Advantages
Universal mounting foot, available for rails NS35 and NS32.
Static connection stability is strong.
High security.
JUT1-95 Series
Product number |
JUT1-95 |
product type |
High current rail terminal block |
Mechanical structure |
screw type |
layers |
1 |
Electric Potential |
1 |
connection volume |
2 |
Rated cross section |
95 mm2 |
Rated current |
232A |
Rated voltage |
1000V |
open side panel |
no |
grounding feet |
no |
other |
|
Application field |
Widely used in electrical connection, industrial. |
color |
Gray, dark gray, green, yellow, cream, orange, black, red, blue, white, purple, brown, customizable |
Wiring Data
line contact |
Stripping length |
33mm |
Rigid Conductor Cross Section |
25mm² — 95mm² |
Flexible conductor cross section |
25mm² — 95mm² |
Rigid Conductor Cross Section AWG |
4-000 |
Flexible Conductor Cross Section AWG |
2-000 |
Size
thickness |
26mm |
width |
83.6mm |
high |
|
NS35/7.5 high |
91.6mm |
NS35/15 high |
99.1mm |
NS15/5.5 high |
|
Material Properties
Flame retardant grade, in line with UL94 |
V0 |
Insulation Materials |
PA |
Insulation material group |
I |
IEC Electrical Parameters
standard test |
IEC 60947-7-1 |
Rated voltage(III/3) |
1000V |
Rated current(III/3) |
232A |
Rated surge voltage |
8kv |
Overvoltage class |
III |
pollution level |
3 |
Electrical Performance Test
Surge Voltage Test Results |
Passed the test |
Power frequency withstand voltage test results |
Passed the test |
Temperature rise test results |
Passed the test |
Environmental Conditions
Surge Voltage Test Results |
-60 °C — 105 °C (Maximum short-term operating temperature, electrical characteristics are relative to temperature.) |
Ambient temperature (storage/transport) |
-25 °C — 60 °C (short term (up to 24 hours), -60 °C to +70 °C) |
Ambient temperature (assembled) |
-5 °C — 70 °C |
Ambient temperature (execution) |
-5 °C — 70 °C |
Relative Humidity (Storage/Transportation) |
30 % — 70 % |
Environmental Friendly
RoHS |
No excessive harmful substances |
Standards and Specifications
Connections are standard |
IEC 60947-7-1 |