Advantages of JUT3-4 Series
Available for rail NS35.
Shock resistance, strong dynamic connection stability.
Easy and fast wiring, high safety.
JUT3-4 Series
Product number |
JUT3-4 |
JUT3-4PE |
product type |
Rail Terminals |
Rail ground terminal |
Mechanical structure |
pull back spring |
pull back spring |
layers |
1 |
1 |
Electric potential |
1 |
1 |
connection volume |
2 |
2 |
Rated cross section |
4 mm2 |
4mm2 |
Rated current |
32A |
|
Rated voltage |
800V |
|
open side panel |
Yes |
Yes |
grounding feet |
no |
Yes |
other |
The total current of all connecting wires must not exceed the maximum load current. |
Please pay attention to the ampacity of the rail. |
Application field |
Railway industry, mechanical engineering, plant engineering, process engineering |
Railway industry, mechanical engineering, plant engineering, process engineering |
color |
gray、customizable |
yellow and green |
JUT3-4 Series Wiring Data
line contact |
Stripping length |
8mm |
8mm |
Rigid Conductor Cross Section |
0.08mm² — 6mm² |
0.08mm² — 6mm² |
Flexible conductor cross section |
0.08mm² — 4mm² |
0.08mm² — 4mm² |
Rigid Conductor Cross Section AWG |
28-10 |
28-10 |
Flexible Conductor Cross Section AWG |
28-12 |
28-12 |
JUT3-4 Series Size
thickness |
6.2mm |
6.2mm |
width |
56mm |
56mm |
high |
|
|
NS35/7.5 high |
36.5mm |
36.5mm |
NS35/15 high |
44mm |
44mm |
NS15/5.5 high |
|
|
JUT3-4 Series Material Properties
Flame retardant grade, in line with UL94 |
V0 |
V0 |
Insulation Materials |
PA |
PA |
Insulation material group |
I |
I |
JUT3-4 Series IEC Electrical Parameters
standard test |
IEC 60947-7-1 |
IEC 60947-7-2 |
Rated voltage(III/3) |
800V |
|
Rated current(III/3) |
32A |
|
Rated surge voltage |
8kv |
8kv |
Overvoltage class |
III |
III |
pollution level |
3 |
3 |
JUT3-4 Series Electrical Performance Test
Surge Voltage Test Results |
Passed the test |
Passed the test |
Power frequency withstand voltage test results |
Passed the test |
Passed the test |
Temperature rise test results |
Passed the test |
Passed the test |
JUT3-4 Series Environmental Conditions
Ambient temperature (operating) |
-60 °C — 105 °C (Maximum short-term operating temperature, electrical characteristics are relative to temperature.) |
-60 °C — 105 °C (Maximum short-term operating temperature, electrical characteristics are relative to temperature.) |
Ambient temperature (storage/transport) |
-25 °C — 60 °C (short term (up to 24 hours), -60 °C to +70 °C) |
-25 °C — 60 °C (short term (up to 24 hours), -60 °C to +70 °C) |
Ambient temperature (assembled) |
-5 °C — 70 °C |
-5 °C — 70 °C |
Ambient temperature (execution) |
-5 °C — 70 °C |
-5 °C — 70 °C |
Relative Humidity (Storage/Transportation) |
30 % — 70 % |
30 % — 70 % |
JUT3-4 Series Environmental Friendly
RoHS |
No excessive harmful substances |
No excessive harmful substances |
JUT3-4 Series Standards and Specifications
Connections are standard |
IEC 60947-7-1 |
IEC 60947-7-2 |