Advantage
Industrial Distribution Terminal Blocks Screw type
Closed bolt leading hole will not only facilitate operation of screwdrivers, also prevent the bolt from dropping out;
Electric potential distribution is realized by either connecting central adaptor to the center of terminal or inserting a side adaptor to the cone jack;
General auxiliaries,such as end plate,segment spacer, and spacer, are attached for terminal with multiple sections;
The insulating shell is made if imported engineering plastic polyamides(Nylon)66,which is of high mechanical intensity, good electrical conductivity, and super flexibility;
Two ends on the top with white marking system to realize uniformed sign.
• 500V
• Good workmanship
• Stable performance
• Easy to install
• Segment test terminal latest structure
• Rich accessories to meet the needs of different occasions
PRODUCT DETAIL DATA
Product properties |
UUK-4/1-2-GY |
UUK-4/1-2PE |
Wiring Diagram |
|
|
Product Classification |
Straight-through terminal block & One-in Two-out |
Ground terminal block One-in Two-out |
Product Type |
Screw Type Terminal Block |
Screw Type Terminal Block |
Product Series |
UUK |
UUK |
Connect Number |
3 |
3 |
Industry |
Power Industry
Factory engineering
process control
Mechanical Engineering
Railway industry |
Power Industry
Factory engineering
process control
Mechanical Engineering
Railway industry |
Potential |
1 |
1 |
Wiring data |
UUK-4/1-2-GY |
UUK-4/1-2PE |
Strip Length |
9 |
9 |
AWG |
24 ~ 10 |
24 ~ 10 |
Rigid conductor cross section |
0.2 mm² ~ 6 mm² |
0.2 mm² ~ 6 mm² |
Flexible conductor cross section |
0.2 mm² ~ 6 mm² |
0.2 mm² ~ 6 mm² |
Minimum wiring capacity of single wire |
0.2 |
0.2 |
Maximum wiring capacity of single strand wire |
6 |
6 |
Minimum wiring capacity of multi-strand wires |
0.2 |
0.2 |
Maximum wiring capacity of multi-strand wires |
6 |
6 |
Incoming line direction |
Side Cable Entry |
Side Cable Entry |
Width(mm) |
6.2 |
6.2 |
Height(mm) |
57.8 |
57.8 |
Deep (mm) |
46.9 |
46.9 |
NS 35/7.5 |
47.5 |
47.5 |
NS35/15 |
55 |
55 |
IEC parameters |
UUK-4/1-2-GY |
UUK-4/1-2PE |
Rated impulse withstand voltage |
6kV |
6kV |
Rated voltage |
500 |
|
Rated current |
32 |
|
UL parameters |
UUK-4/1-2-GY |
UUK-4/1-2PE |
Rated voltage |
|
|
Rated current |
|
|
Material specifications |
UUK-4/1-2-GY |
UUK-4/1-2PE |
Color |
Grey |
Yellow & Green |
Flammability rating |
V0 |
V0 |
Pollution level |
3 |
3 |
Insulation material group |
I |
I |
Insulation Materials |
PA66 |
PA66 |
Standards and Norms |
UUK-4/1-2-GY |
UUK-4/1-2PE |
Connections comply with standards |
IEC 60947-7-1
GB14048.7.1 |
IEC 60947-7-2
GB14048.7.2 |